Senin, 28 Juli 2008

Electrical Safety "Grounding"

Saya dapat ini dari sebuah Blog yang cukup bagus dan saya Post ulang...di Blog ini karena ada hubungannya dengan Blog Elctrical Instrumentation ini...

GROUNDING

A good ground connection is essential to the safe and reliable operation of any piece of electrical equipment. Electrical grounding ensures that if there is ever a short circuit on a piece of electrical equipment, current will flow through the ground system and trip a breaker or blow a fuse.
A grounded outlet has three holes for each plug. In a properly wired outlet, the rounded slot is the ground connection. A grounded outlet must be used correctly:

* Never cut off the third grounding prong on an appliance plug.
* Don’t try to install a grounded outlet in an ungrounded outlet box.
* Use “cheater” adapter plugs only on a temporary basis. Use ony if the outlet box is grounded, and make sure the small metal circle or the pigtail adapter contacts the screw in the middle of the outlet.

Ground Fault Circuit Interrupt

For an added measure of protection, outlets near water sources, like sinks and laundry appliances, as well as all garage and outdoor outlets, should have a ground fault circuit interrupter (GFCI). These are the outlets with the “test” and “reset” buttons.


A GFCI works by monitoring the flow of electricity through the outlet’s circuit. If there is any variation in the current, the GFCI will automatically cut off the flow of electricity, preventing injury. According to the Consumer Products Safety Commission, if every household used GFCIs, deaths from electrocution in and around the home could be reduced by 50 percent.

There are four types of GFCIs:

* “Whole-house” devices for circuit panels that protect against external power surges. These should be installed only by a certified electrician.
* Whole circuit devices for circuit panels, that are used in place of circuit breakers. These should be installed only by a certified electrician.
* Receptacle-based protectors that replace standard wall outlets. You can install these yourself by carefully following manufacturer’s instructions.
* “Portable” units that simply plug into a wall outlet. Any homeowner can use this type.

GFCIs should be tested every month. Plug a lamp or radio into a GFCI outlet and turn it on. Push the “test” button on the outlet; the lamp or radio should turn off immediately. If it doesn’t, the GFCI has been wired improperly or is no longer functioning.

GFCIs are inexpensive and provide the best protection against electrical hazards, and we strongly recommend using them in your home. But remember, even the best GFCI can’t offer 100% protection, so never forget other electrical safety rules



GROUNDING SYSTEM FOR ELECTRIC FENCE

The majority of electric fence problems relate to grounding concerns. This factsheet looks at the
two methods of system grounding commonly used and how to test a grounding system.



THE EFFECT OF SOIL CONDITIONS

Electric fences are designed so the animal will complete the electrical circuit upon touching the fence wire. This forms the closed circuit required for electrons to flow. For simplicity, the standard electric fence uses the earth as the “return” leg of the circuit. This is only effective if the conductivity is good, as in moist soil.


If the soil is dry, frozen or snow covered the conductivity is reduced which reduces the effectiveness of the electric fence. For areas that receive 24 inches or less annual precipitation (or where the precipitation is poorly distributed throughout the year), a “wire return” system should be used.


GROUNDING IN MOIST EARTH CONDITIONS ( Earth Return )


This is the standard grounding situation. The moisture in the earth is sufficient to allow a flow of electrical current that will ensure a shock occurs. The critical component is the soil contact of the grounding rods. They connect the earth return current flow to the controller and must have good soil contact to ensure this flow is not restricted.

This requires:

* For safety reasons, a location for the grounding system that is at least 7 feet from any other electrical or telephone grounding system and from any building foundation (especially a dairy barn) or underground water piping
* A location where the wiring cannot be easily damaged or disconnected by livestock or machinery (see below regarding burial)
* A minimum of 3 galvanized steel earthing rods, driven into moist earth; (these need not be located right at the fence controller but must be at a moist earth location)
* A separation space between the rods of 6 feet
* A continuous length of wire for connection between the rods and the controller
* A standard electrical grounding clamp (noncorrosive) for each rod/wire connection.

A grounding system that will meet the Electrical Code for grounding uses the following standard electrical components:

* Galvanized steel ground rods, 6 feet x 5/8 inch diameter,
* Brass or copper clamps, and
* #6 bare copper wire from rods to controller.

Although a smaller wire size may be adequate, a #6 wire may be directly buried which is a good method to protect the system from damage. The grounding rods can be driven 6 or 8 inches below the earth surface, say into a small dug depression. The wire can be laid into a shallow trench, clamped to the rods, then buried. The wire may be buried all the way to the fence controller.

Note that where this controller ground is near a building with an electrical service, the wire from the ground rods to the controller should be insulated to avoid ‘cross grounding’.
In addition to this main grounding of the fence controller, secondary grounding of the nonelectrified fence wire(s) may be done as explained for the “wire return” systems.



GROUNDING IN DRY EARTH CONDITIONS ( Wire Return )

In dry, frozen or snow covered conditions the earth return system is not sufficient to ensure current flow that will produce a shock.

In these conditions, one or more fence wires are used for the return circuit to the fence controller (in addition to the earth return grounding of the fence controller). This method ensures a circuit when the animal touches both an energized wire and a grounded wire (in semiwet conditions, some current may also flow via the earth return). A shock then occurs even in these poor earth return conditions (i.e. dry, frozen or snow covered).

The nonelectrified fence wire(s) are connected to the main fence controller grounding system as well as to single groundrods located approximately every ½ mile along the fence line (more frequently in very dry conditions). These ground rods are the same as the main grounding rods. To ensure the animal can easily contact a “hot” wire and a grounded wire and there by receive a shock, alternating fence wires may be electrified and grounded. However, while being more effective, it may cause maintenance problems as any debris that may contact the fence wires will more easily short out the circuit then if contacting a “hot” wire and the earth.



SALT CORE GROUND RODS

For very dry sites the main ground rods may have high resistance to current flow. This can be greatly reduced by using the following technique (which adds salt around the ground rods to increase the soil
conductivity and a clay material to hold moisture):

* Auger or dig 3 holes for the ground rods that are at least 3 inches diameter by 4 feet deep, spaced 35 feet apart
* Fill each hole with a wet slurry of 2 parts Bentonite (a clay material sometimes called “driller’s mud”) and 1 part coarse salt
* Place a 4 foot by ½ or ¾ inch diameter stainless steel tube down the center of the hole (stainless because of the corrosive nature of salt)
* Cover the area with an inch or two of sand to reduce evaporation.

The ground wire is clamped to these tubes as before.
To ensure continued low resistance, these salt core ground rods can be watered during drought conditions.


TESTING THE GROUND SYSTEM

The earth return system of grounding a fence controller relies on the soil moisture conditions for current flow and these conditions change throughout the year.

To ensure continued fence performance, a yearly grounding check should be made, preferably at the driest season the fence is being used. The following procedure should be followed:

* About 300 feet from the controller connection to the fence, use 3 or 4 steel fence posts (or similar steel material) to create a dead short from an energized wire to the earth
* This will reduce the fence line voltage to less than 1000 volts and put the grounding system under load with a high flow of electrons trying to get through the soil back to the energizer
* Using a volt meter (suitable for electric fences), measure the voltage between the ground wire to the controller and the earth at least 3 feet from any ground rod
* If the grounding system is adequate the flow will all be handled by the ground rods and the meter reading will be very low (200 volts or so)
* A higher meter reading will indicate the grounding system cannot handle the flow and more ground rods are required
* Add another ground rod and repeat the test.



(An optional method is to skip the meter and simply grasp a ground rod with one hand and touch the earth with the other hand. A poor ground is indicated with a shock, the severity of which will depend upon the condition of the grounding system. This is not recommended except for the foolhardy.)




Thanks Bro... Tjetjep

Tidak ada komentar: